Skip to content

Transformer validation #1755

Open
Open

Description

@acostarelli

Currently TransformerCircuits with VOLTAGE control can have control_limits that disagree with the regulated_bus's own voltage_limits. We should either take the tighter of each bound or raise an error, open to opinions about either.

And if we aren't already, we should make sure these (and other) limits are finite, non-negative (depending on control), and ordered.

Activity

  1. self-assigned this
    on Aug 14, 2026
  2. added theissue type on Aug 14, 2026
  3. acostarelli commented on Aug 14, 2026

    @acostarelli
    MemberAuthor

    Example downstream issue: on polar networks we have a voltage magnitude variable bounded by voltage_limits that might later conflict with the control constraints.

  4. m-bossart commented on Aug 14, 2026

    @m-bossart
    Contributor

    Both bus voltage limits and voltage control limits default to [0.9-1.1] in PSSE. I think during parsing we should warn if the control voltage limits falls outside of the bus limit that it is controlling and set the control voltage to the bus voltage.

  5. acostarelli commented on Aug 14, 2026

    @acostarelli
    MemberAuthor

    Additional validation: multiple circuits with the same regulated bus. Maybe they have to also have limits that agree, or maybe they shouldn't be allowed at all.

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment